Typically, most of the work recommended or required for changing from summer to winter modes is mechanical-related. I have listed below some items that are control related.
- Outdoor air units verify proper functionality of dampers:
- An area often overlooked is the outdoor air dampers. These are often out of adjustment, or not functioning at all. Properly maintained outdoor air dampers are an area for potential energy savings as well.
- Low ambient air safeties are in place and functional
- One of the items we deem critical for preheating season checks is the low ambient safeties. We verify they are in place, with no apparent damage, and functional. This allows protection for the heating/cooling coils in an air handler unit.
- Verify that Low ambient protection controls sequence is functioning properly
- If applicable we like to verify the low ambient control sequence is in place and functional. This is where when a unit trips because of low ambient air temperatures inside a unit the controls would open the valves and start the pumps to maintain a flow until the reason for the tripped safety can be determined and corrected. The intent is to prevent the freezing of a coil inside the unit.
- Verify proper operation of gas valve and heating valves
- We like to verify the proper operation of heating valves in VAV boxes and gas valves where applicable. This allows for better occupant comfort during the winter months.
- If appropriate verify Boiler functionality and confirm controls sequences
- When a customer has a boiler, we try to coordinate with the customer’s mechanical contractor to go over the operation and verify the controls sequence is working as designed prior to heating season.
- Verify proper operation and CFM discharge of VAV boxes with electric reheat
- When a VAV box (Variable Air Volume) with electric reheat, it is important to verify airflow. This ensures that heat will be there when called for, allowing for better occupant comfort and less cold spots through out the building.
If your company isn’t sure the best protocols for managing these control-related issues, call us for an assessment. Reach us at 800-567-1180.